PULSER Triac controller for electric heating, single phase or two phase

PULSER Controller for electrical resistances with automatic adaptation to 230 V AC or 400 V AC

Complete electric heating controller with builtin
sensor and setpoint adjustment.
• External sensor and external setpoint can
be connected.
• Control function adapts automatically, using
PI for supply air control and P for room control.
• For loads up to 3.6kW (230 V) or 6.4kW
(400 V).
• Automatic adaption to connected supply
voltage 210…415 V.
• Adjustable night set-back, 0…10K.

PULSER/D Triac controller for electric heating Single phase or two phase

PULSER/D is an electric heating controller for controlling electric heating batteries, electric panels etc.
The controller can be connected to single phase or two phase 210 … 415 V AC.
Triac controller for electric heating
Single phase or two phase
section position
PULSER/D
PULSER/D is intended for DIN-rail mounting in a
cabinet.
For loads up to 3.6kW (230 V) or 6.4kW (400 V).
Automatic adaption of control function, P or PI-control.
Automatic adaption for supply voltage 200 – 415 V.
Night set-back 5K.

PULSER-ADD Slave-controlled add-on unit for electric heating controller, single phase or two phase

PULSER-ADD
Slave-controlled add-on unit for electric heating controller, single phase or two phase
• Supplementary unit for slave control from
another PULSER.
• For loads up to 3.6 kW (230 V) or 6.4 kW
(400 V).
• Automatic adaptation to connected supply
voltage, single phase or two phase 200…415 V.
• Several PULSER-ADD can be slave controlled
by the same main unit

PULSER-M Single phase / two phase controller for electric heating with minimun / maximum limitation.

PULSER-M
Single phase / two phase controller for electric heating with minimun / maximum limitation.

Complete controller with built-in sensor
and setpoint adjustment
• Function for minimum / maximum limitation
• For loads up to 3.6 kW (230 V) or
6.4 kW (400 V)
• Automatic adaption of control function,
P or PI-control
• Can be connected to an external sensor or
a potentiometer
• Adjustable night set-back 0…10K